Sale!

OT-88-05-1 — Investigation of Heat Transfer and Pressure Drop Augmentation for Turbulent Flow in Spirally Enhanced Tubes

Original price was: $15.00.Current price is: $7.50.

Conference Proceeding by ASHRAE, 2008

Category:

Description

The performance of spirally enhanced tubes is discussed in this paper in terms of heat transfer enhancement, friction factor enhancement, and enhancement efficiency as a function of a single nondimensional geometric parameter, the severity. Heat transfer and friction factor data from more than 60 different tubes are shown to collapse to a single curve with minimal scatter when plotted as a function of the severity. It is shown that in turbulent flow the increase in friction factor is usually much larger than the corresponding increase in heat transfer. In addition, values of severity between 0.001 and 0.01 are shown to yield optimum enhancement for turbulent flow.

Units: Dual

 

Citation: Symposium, ASHRAE Transactions, 1988, vol. 94, pt. 2, Ottawa

Product Details

Published:
2008
Number of Pages:
13
File Size:
1 file , 1.3 MB
Product Code(s):
D-OT-88-05-1