Investigates the energy-saving potential of using indirect evaporative coolers to precool incoming outdoor air as the first stage of a standard cooling system. States that for dry and moderately humid locations, either exhaust room air or outdoor air can be used as the secondary air to the indirect evaporative precooler with similar energy savings. Under these conditions, the use of outdoor air is recommended due to the simplicity in installing the duct system. For humid locations, the use of exhaust room air is recommended because the precooling capacity and energy savings will be greatly increased. For locations with short cooling seasons, the use of indirect evaporative coolers for precooling may not be worthwhile. Also gives some simplified indices for easily predicting the precooling capacity, energy savings and water consumption of an indirect evaporative precooler. States these indices can be used for cooling systems with continuous operation, but further work is needed to determine whether the same indices are also suitable for cooling systems with intermittent operations.
KEYWORDS: Cooling, precooling, outdoor air, evaporative coolers, evaporative cooling, energy conservation.
Citation: ASHRAE Transactions 1993, Vol.99, pt.1