Sale!

2922 — Ventilation Measurements in Large Office Buildings

Original price was: $15.00.Current price is: $7.50.

Conference Proceeding by ASHRAE, 1985

Category:

Description

Ventilation rates were measured in nine office buildings using an automated tracer gas measuring system. The buildings range in size from a two-story federal building with a floor area of about 220,000 ft² (1900 m²) to a 26-story office building with a floor area of 700,000 ft² (65,000 m² ). The ventilation rates were measured for about 100 hours in each building over a range of weather conditions. The results are presented and examined for variation with time and weather. In most cases, the ventilation rate of a building is similar for hot and cold weather. In mild weather, outdoor air is used to cool the building and the ventilation rate increases. In the buildings where infiltration is a significant portion of the total ventilation rate, this total rate exhibits a dependence on weather conditions. The measured ventilation rates are discussed in relation to the outdoor air intake strategy in each building. The ventilation rates are also compared to design rates in the buildings and ventilation rates based on ASHRAE Standard 62-81. Some of the buildings are at times operated at lower ventilation rates than recommended in Standard 62-81.

Units: Dual

 

Citation: ASHRAE Transactions, 1985, vol. 91, pt. 2A, Honolulu, HI

Product Details

Published:
1985
Number of Pages:
15
File Size:
1 file , 1.2 MB
Product Code(s):
D-HI-85-2922