Sale!

3004 (RP-221) — An Experimental Investigation of Pressure Drop in Forced-Convection Condensation and Evaporation of Oil-Refrigerant Mixtures

Original price was: $15.00.Current price is: $7.50.

Conference Proceeding by ASHRAE, 1986

Category:

Description

Experimental measurements of pressure drop have been made for forced-convection evaporation and condensation of oil-refrigerant (R-12) mixtures inside a horizontal tube, Data were compared to a wide range of frictional pressure drop and void fraction relationships. The best representations for the oil-free data were then modified to better correlate both oil-free and oilrefrigerant results. For condensation, a modification of the prediction given by the Lockhart- Martinelli relation for frictional pressure drop and the homogeneous void fraction model is presented. For evaporation, the prediction given by the Dukler II frictional pressure-drop correlation and the homogeneous void fraction is modified. These relationships predict the pressure drop for 85% of the data to within ±35%. The added oil increased the pressure drop 2% to 6% for condensation and 63% to 86% for evaporation.

Units: Dual

 

Citation: ASHRAE Transactions, 1986, vol. 92, pt. 2A, Portland, OR

Product Details

Published:
1986
Number of Pages:
12
File Size:
1 file , 1 MB
Product Code(s):
D-PO-86-3004