Description
Experiment shows that chilled water cooling coils operating at low water-side Reynolds numbers do not perform as well as predicted by manufacturer’s software. At a Reynolds number of 3100 there is an 8% over-prediction and this increases with decreasing Reynolds number. An alternative correlation is suggested to predict the heat transfer coefficient.
KEYWORDS: calculating, performance, heat flow, chilled water supply, water flow, Reynolds numbers, cooler batteries, chilled water supply.
Citation: ASHRAE Transactions 1993, Vol.99, pt.1
Product Details
- Published:
- 1993
- Number of Pages:
- 11
- File Size:
- 1 file , 1.1 MB
- Product Code(s):
- D-17603