Description
A three-dimensional numerical investigation of the airside performance of fin-and-tube heat exchangers having round and oval configurations is presented in this paper. For louver fin geometry at a fixed louver length, a 10% decrease in heat transfer performance is observed and a 41% decrease of pressure drop is seen for the oval tube configuration. For the plain fin configuration and V fr < 2 m/s (6.56 ft/s), the heat transfer performance for an oval tube is slightly higher than that of a round tube. However, the heat transfer performance is reversed when V fr < 2 m/s (6.56 ft/s) . The pressure drop for plain fin and oval tubes shows 100% lower pressure drop when compared to the round tube configuration.
Units: Dual
Citation: Symposium, ASHRAE Transactions, vol. 106, pt. 2
Product Details
- Published:
- 2000
- Number of Pages:
- 7
- File Size:
- 1 file , 330 KB
- Product Code(s):
- D-7285